compressor load switch - fuse
Product Detailed

Isolate Switch
1.Type:FKN12A-12
2.Standard|:IEC420 GB3804
3.Main Material:Procelain&Steel

Main purpose
      FKN12A-12DCompressed air load switch, FKRN12A-12D series of compressed air load switch - fuse for 12kV and below three-phase power distribution system, as transformers, cables, overhead lines and other electrical equipment, control and protection purposes; especially suitable for urban and rural power network terminal substation and box-Model substation. And applies to ring, dual power supply unit of radiation control and protection.
      FKN12A-12DSeries pressuring gas division and the load current load switch and overload currents.
      FKRN12A-12D series of compressed air load switch - fuse to division and load current, overload current, short-circuit breaking current.

Use of environmental conditions
      Ambient air temperature    Limit +40°C  Lower -25°C
      Above sea level1000m.
      Relative humidity: daily average is less than 95%, on average less than 90%;
      Seismic intensity of not more than 8 degrees;
      No fire, explosion, chemical corrosion and severe vibration in the workplace;
      Contamination level:II.

Structural characteristics
     Load switch, grounding switch, fuse and institutions in a framework, it can be flexibly combined, compact structure, small size and ease of installing;
     Fracture for the direct-acting Model layout, dynamic and thermal parameters of high current, one-time to complete the operation;
     Static contact with insulation cover, so that the structure of ring counters implemented in isolation, eliminating the white insulated partition, fracture insulation flapper to prevent cabinet arc short circuit;
     The valve has a unique structure, the load switches gate, the door automatically isolate the fracture, protective and good;
     Load switches and earthing switches, fuses reliable mechanical lock between the devices meet the "Five Anti" requirements;
     With manual operation and the operation of AC and DC electric power operations in two forms, easy to implement power system of the "three remote" requirements.

Main technical parameters

Serial numberProjectUnitParameters FZN21FZRN21
1Rated voltageKV1212
2Rated frequencyHz5050
3Rated CurrentA630125
4Rated insulation level1min power frequency withstand voltageOn the ground, and whitekV4242
Isolated fracture4848
Lightning impulse withstand voltage (peak)On the ground, and white7575
Isolated fracture8585
5Rated short time withstand current /td>Load SwitcheskA20——
Grounding switch20
6Rated short circuit durationLoad SwitchesS4——
Grounding switch2
7Rated short circuit making current (peak)kA50——
8Rated breaking currentActive load breaking currentA630——
Closed-Loop breaking current630——
5%Active load breaking current31.5——
Cable charging current10——
Breaking load transformerKVA1250
9Rated short-circuit breaking current (current-limiting fuses)kA——31.5
10Rated transfer currentA——1200
11Mechanical lifeTimes20002000
12Impact energy outputJ——1+0.5

Serial numberNameUnitData
1Open fracture frommm≥175
2Phase center distance210±2
3White air gap≥125
4Travel210±4
5S../uper Stroke≥40
6Different closing phase ofms≤10
7Different points of three-phase gate≤5
8Shunt trip inherent Tripping timems40~65
9Main Loop resistanceμΩ≤130