Andeli Group Co., Ltd.

DZ49-63 series miniature circuit breaker

DZ49-63 series miniature circuit breaker
Product Detailed

DZ49-63 is applicable to a line of AC 50Hz/60Hz, 230V in single pole, 400V in double, three,four poles for protecting overload a

1.Application

DZ49-63 is applicable to a line of AC 50Hz/60Hz, 230V in single pole, 400V in double, three,four poles for protecting overload and short circuit, and rated current up to 63A. It can also beused for infrequent line conversion under the normal condition.The breaker is applicable tolighting distribution system in industrial enterprise, commercially district, high-rise building anddwelling house. It conforms with the standards of IEC60898.

2.Main Technical Parameter

Type DZ49-63
Pole1P2P, 3P, 4P
Rated current (A)6,10,16,20,25,32,40,50,63
Rated voltage(V)230400
Ambient temperature-5 oC~+40 oC
Type of instantaneous releaseCDCD
Rated short circuit breaking capacity(KA)1-32A: 6
50-63A: 4
41-32A: 6
50-63A: 4
4

3.Applicable conducting wire

Rated current(A) Nominal cross section of wire mm2
1-6A1
10A1.5
16,20A2.5
25A4
32A6
40,50A10
63A16


4.The over-current protection property

Ambient Temperature Initial Status Test Current Expected Result Expected Result Note
30±2 oCCold position1.13Int≥1hNon-release-
Carried out immediately after previous test1.45Int<1hRelease-
Cold position2.55In1s<t<60s
(In≤32A)
ReleaseCurrent smoothly rises to specified value within 5s
Cold position2.55In1s<t<120s
(In>32A)
Release
-5~+40 oCCold position3Int≥0.1sNon-releaseType B
Cold position5Int<0.1sReleaseType B
Cold position5Int≥0.1sNon-releaseType C
Cold position10Int<0.1sReleaseType C
Cold position10Int≥0.1sNon-releaseType D
Cold position20Int<0.1sReleaseType D



Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.